Home Systems Guide · No. 3 · Theory guide, set v2 · draft 1
Insulation
How heat, air and moisture cross the envelope of a two-story wood-frame house under a truss roof, what limits each assembly, and what the energy code requires when an assembly is opened.
Refer to the following guides for concepts:
- Framing (truss uplift and slip joints, no cutting of truss members, dead load of a floor topping)
- Soundproofing (cavity fill as an acoustic requirement, decoupling, the partition-head gap as a sound path)
- Windows & Exterior Doors (whole-window U, glazing code values, rough-opening seal)
- HVAC, DHW & Ventilation (design loads, radiant emission coefficients)
Applied to this house: House Project Guide, chapter 3
Read this first
- R-value describes conduction only, so air leakage and radiation, which it leaves out, can match or exceed it at some surfaces. Part 1
- In a 2×4 wall the studs cap the assembly: no cavity fill reaches the new-construction wall value, and with the framing fixed only continuous insulation moves the cap. Part 2
- A standard truss heel thins the insulation at the eave, so a nominal R-49 ceiling performs near R-40 and the code's two ceiling routes are different requirements. Part 3
- At the ceiling plane air transport is larger than conduction once the attic is deep, so sealing acts on the larger term and added depth on the smaller. Part 4
- The garage puts two boundary surfaces in the middle of the house, and both read as interior construction, so their fill is easy to miss. Part 4
- Stucco walls in IECC zone 3 can dry toward the interior, so a low-perm interior layer carried over from cold-climate practice removes their drying path. Part 5
- Heating a slab changes its rules: the edge loss rises and Title 24 makes slab insulation mandatory. Part 6
- Most of the code's insulation requirements are triggered by what the work touches, not by the house as a whole. Part 8
| Decision | Depends on | Treated in |
|---|---|---|
| D1 Ceiling plane and attic: seal, add depth, or both; vented attic kept or moved to the roof deck | Existing depth; heel height and pitch; leakage and its location; anything mechanical in the attic; recessed fixture plan | Part 3, 4 |
| D2 Exterior walls that are opened: cavity fill, and whether interior continuous insulation is added | Framing fraction; room depth available; drying direction; fire barrier over foam | Part 2, 5 |
| D3 Garage boundary: floor over the garage and the shared walls | Whether the cavities are filled now; joist depth; the fire-rated membrane | Part 4 |
| D4 Slab: left unheated, or heated with which insulation route | The radiant floor or ceiling decision; floor height available; slab and footing as built | Part 6, 8 |
| D5 Compliance route: prescriptive alteration values or the performance path | Which provisions the work triggers; climate zone; whether credits such as QII are claimed | Part 8 |
| Part | Ceiling and attic | Exterior walls | Garage boundary | Slab |
|---|---|---|---|---|
| 1 · Heat flow | Series and parallel paths; the envelope on one axis | |||
| 2 · Walls | — | Framing cap, continuous insulation | Shared walls use the same arithmetic | — |
| 3 · Ceiling | Heel taper, depth, attic strategies, summer gain | — | — | — |
| 4 · Air and the boundary | The largest leakage surface | Penetrations, rim joist | Air and contaminant barrier | Edge at the garage line |
| 5 · Moisture | Air-transported moisture into the attic | Drying direction | — | Slab moisture under finishes |
| 6 · Ground and radiant | Backing behind a ceiling panel | — | — | Edge loss, heated slab |
| 7 · Interior cavities | Partitions and the floor between stories: acoustic and fire properties of the fill | |||
Table 1 maps the parts to the boundary surfaces. Subsections that cover one surface carry an Applies to tag; untagged subsections apply generally. An Informs tag marks the subsections behind each decision above.
1 · Heat flow: what R-value describes and what it omits
Bottom line. Resistances add in series and conductances add in parallel by area, and the number on a product label covers conduction through one uniform layer only.
Resistances add in series; conductances add in parallel
R resistance, h·ft²·°F/Btu · fⱼ area fraction of path j · Q heat flow, Btu/h
layers along one path stack their resistances; side-by-side paths share the area and the weakest dominates.
R-value is measured in steady state on a uniform layer. Four things that matter in a house are outside it:
- Framing in parallel with the insulation (Part 2).
- Non-uniform thickness, such as the taper at a truss heel (Part 3).
- Air moving through or around air-permeable insulation (Part 4).
- Radiation across air spaces and heat storage, which shape summer attic gains (Part 3).
Film and layer values used throughout: interior films R-0.68 (vertical), 0.61 (heat flow up), 0.92 (heat flow down); exterior film R-0.17; softwood R-1.25 per inch; RSI = R ÷ 5.678.
The envelope on one axis: UA by component
Putting every surface in UA (Btu/h·°F) shows where heat leaves before any cost or effort enters. Air leakage enters as a UA equivalent, 1.08 × cfm. For the reference house (2,300 sf, two stories, R-13 walls, 300 sf of original clear dual-pane glazing, 6 ACH₅₀, garage cavities taken as empty) the total is about 873 Btu/h·°F (Figure 1).
Table 2 lists the components and their bases.
| Component | Area, sf | Coefficient | UA, Btu/h·°F | Share |
|---|---|---|---|---|
| Windows, existing clear dual pane | 300 | U 0.78 | 234 | 27% |
| Exterior walls, R-13 cavity | 1,935 | U 0.088 | 170 | 19% |
| Garage–house walls, uninsulated | 405 | U 0.268 | 108 | 12% |
| Floor over garage, uninsulated | 500 | U 0.214 | 107 | 12% |
| Air leakage, whole house (annual average) | — | 92 cfm | 99 | 11% |
| Slab edge, uninsulated | — | F 0.73 × 105 ft | 77 | 9% |
| Ceiling, R-30 with heel taper | 1,400 | U 0.0341 | 48 | 5% |
| Exterior doors | 60 | U 0.5 | 30 | 3% |
Reference geometry: 1,400 sf ceiling on a 150 ft perimeter, 1,935 sf net opaque wall, 405 sf of garage–house wall, 500 sf of floor over the garage, 105 ft of exposed slab edge. Air leakage is the annual-average natural rate, ACH₅₀ ÷ 20. Design heat loss is UA × design ΔT (HVAC · Design heating load).
The ranking is on the magnitude axis only. Per square foot the glazing is about nine times worse than the wall; per dollar of change the order depends on access and price. Title 24 required R-13 walls and R-19 floors at the garage throughout this era, and many houses have them; filled to those levels the two garage rows total about 59 Btu/h·°F instead of 215, and the reference case takes them as empty to show what an unfilled bay costs.
2 · Walls: the framing caps a 2×4 assembly
Bottom line. Over a whole elevation about a quarter of a 2×4 wall is wood, and that path sets a floor on U that no cavity fill can pass.
Parallel paths: cavity and framing
Ceiling and atticExterior wallsGarage boundarySlab
Informs D2
Studs, plates, headers, corners and partition backing occupy about 25% of a 2×4 elevation (Title 24 Reference Joint Appendix JA4, ASHRAE 90.1 Appendix A), well above the 9% counted from studs alone. Each path carries the same exterior and interior layers, R-2.13 for stucco, paper, ½ in plywood, ½ in gypsum and films (Figure 2).
framing fraction 25%; R_cavity installed fill R
the cavity term shrinks as fill improves, and the framing term stays put.
Table 3 gives the assembly values for the common fills.
| Cavity fill | Assembly U | Effective R | Share through framing |
|---|---|---|---|
| R-11 batt | 0.096 | 10.5 | 40% |
| R-13 batt (reference existing) | 0.088 | 11.4 | 44% |
| R-15 high-density batt | 0.082 | 12.2 | 47% |
| Closed-cell foam, 3½ in | 0.069 | 14.6 | 56% |
| Cavity R → ∞ | 0.0384 | 26 | 100% |
Reaching U-0.048, the new-construction prescriptive wall value in climate zones 3–4, from inside the cavity would need R-76 in 3½ in. That value was set for 2×6 framing with continuous insulation. The 2025 mandatory value for a 2×4 wall, U-0.095, is met by R-13 or R-15 batts in this build-up (Figure 3).
Sensitivity to framing fraction
| Framing fraction | U with R-15 | Asymptote |
|---|---|---|
| 15% | 0.073 | 0.023 |
| 20% | 0.077 | 0.031 |
| 25% | 0.082 | 0.038 |
| 30% | 0.087 | 0.046 |
A measured framing take-off changes the numbers, not the conclusion: at 15% framing the R-15 wall is U-0.073, and the cavity-only route to U-0.048 still needs about R-42 (Table 4).
With the framing fixed, continuous insulation is the lever on the asymptote
Ceiling and atticExterior wallsGarage boundarySlab
Informs D2
With the framing fixed, a layer across the studs is the one change that adds its full R to both paths. With exterior work out of scope, it goes on the interior face under furring and new gypsum. Over an R-15 cavity, R-7.6 of continuous insulation reaches U-0.048.
| Board | R per in | Board, in | With furring and gypsum, in | Vapor behavior |
|---|---|---|---|---|
| Polyiso, foil-faced | 5.9 | 1.3 | 2.7 | Class I facer |
| XPS | 5.0 | 1.5 | 2.9 | Class II |
| Mineral wool board | 4.2 | 1.8 | 3.2 | Vapor-open |
| EPS | 4.0 | 1.9 | 3.3 | Class III |
Room depth adds ¾ in furring and ⅝ in gypsum over the board; foam plastics also need a thermal barrier (CRC R316), which the gypsum provides.
Across the reference wall area the change from the existing R-13 to U-0.048 is a ΔUA of about 77 Btu/h·°F, the largest change available on the opaque exterior walls; replacing the windows (Windows & Doors · Energy value) and filling an empty garage floor are of similar or larger size. It is also the only measure here that consumes floor area, which partitions already draw on (Soundproofing · Partition assemblies). Foil-faced polyiso is the thinnest and reverses the wall's drying direction; mineral wool board keeps it (Part 5).
Closed-cell foam in a 2×4 cavity gains little over a batt because the framing still governs (Table 3), and it blocks inward drying, bonds both faces of the wall together and is not reversible.
3 · Ceiling and attic: depth, the heel and summer gain
Bottom line. A vented truss attic can take deep insulation cheaply in the field and very little at the eave, and above about R-38 depth buys little winter energy.
A standard truss heel thins the insulation at the eave
Ceiling and atticExterior wallsGarage boundarySlab
Informs D1
Where a truss bears on the wall, the space between the top plate and the roof sheathing is the heel height, about the top-chord depth (3½–5½ in) for a standard heel. CRC R806.3 keeps 1 in clear under the sheathing at the vents, so a 4 in heel leaves 3 in of insulation at the wall line. Depth then grows at the roof pitch (Figure 4).
h heel height · c vent clearance · s roof slope · r R per inch · L band width · R_nc films and gypsum
insulation depth grows linearly from the wall, so the band's average U is a logarithm rather than the field value.
Table 6 carries the taper through the common nominal levels.
| Nominal | Field depth, in | Taper band, ft | Share of ceiling | Weighted U | Effective R |
|---|---|---|---|---|---|
| R-19 | 5.4 | 0.61 | 6% | 0.0493 | 20 |
| R-30 | 8.6 | 1.39 | 14% | 0.0341 | 29 |
| R-38 | 10.9 | 1.96 | 20% | 0.0287 | 35 |
| R-49 | 14.0 | 2.75 | 27% | 0.0245 | 41 |
| R-60 | 17.1 | 3.54 | 34% | 0.0219 | 46 |
| R-75 | 21.4 | 4.61 | 43% | 0.0198 | 51 |
4:12 pitch, 1 in clearance, loose fill at R-3.5 per in, 1,400 sf on a 150 ft perimeter with eaves on all four sides (hip). A gable roof has eaves on the two long walls only, so the band scales with eave length: with 80 ft of eave, R-49 covers 16% of the ceiling in taper and performs near R-45.
Nominal R-49 performs at about R-41. Title 24 §150.2(b)1J offers R-49 for the insulation alone or a weighted U-0.020 as alternatives; at a 4 in heel under a hip roof the weighted route needs about R-73 nominal, a 21 in field, so the two are different requirements. An exception in the same section accepts filling the available space where it cannot hold the required value without blocking ventilation (Figure 5).
Attic strategies compared
Ceiling and atticExterior wallsGarage boundarySlab
Informs D1
Table 7 compares the four approaches for a vented truss attic.
| Strategy | Strengths | Limits | Fit |
|---|---|---|---|
| A · Seal the ceiling plane, then blow fill to a marked settled depth | Acts on the two largest ceiling terms, leakage and conduction; keeps the roof deck outside and its drying path open; reversible | Truss webs limit access and depth checks; the eave taper remains; each fixture added later reopens the sealed plane | Default for a vented truss attic with nothing mechanical in it |
| B · Method A plus a radiant barrier | Cuts radiant exchange from the deck by about 94%; part of the Title 24 Option C package | Value falls as ceiling R rises and as attic ducts disappear; dust degrades an attic-floor barrier | Summer comfort upstairs, not annual energy |
| C · Unvented attic: insulation at the roof deck (CRC R806.5) | Brings the attic inside; removes the taper and the leaky ceiling plane from the boundary | Spray foam over a sloped area larger than the ceiling; encapsulates webs and connector plates; changes the deck's moisture regime; several times the cost | Justified mainly where ducts or equipment must sit in the attic |
| D · Mandatory minimum where the ceiling is opened | No added cost | Leaves the leakage and depth terms as they are, at the time access is easiest | Legal where §150.2(b)1J is not triggered |
Depth has a sharply falling return on the energy axis because the taper and the field both flatten. In the reference house, R-30 to R-49 saves about $27 a year in heating and R-49 to R-60 about $7 (Figure 6). The case for depth past R-38 rests on summer comfort and on the roof-borne sound path (Soundproofing · Roof and attic path), not on payback.
Under R806.3 every vented bay keeps a baffle and 1 in of clearance. Insulation blown against the soffit closes the vents that are the attic's moisture control, and baffles and depth dams attach to sheathing, plates or chord faces, never to a cut web (Framing · No truss member is cut).
Summer gain under a tile roof depends on radiation and heat capacity
Ceiling and atticExterior wallsGarage boundarySlab
Informs D1
ε emittance of the two surfaces · α thermal diffusivity
radiant exchange across the attic falls with the lower emittance; a material with more heat capacity per volume delays the afternoon peak.
With both surfaces at ε 0.9, F_e = 0.82; with one foil face at ε 0.05 it is 0.050, a 94% cut in the radiant term only. Cellulose has about four times the heat capacity per volume of loose fiberglass (ρc_p 0.5–1.2 against 0.1–0.3 Btu/ft³·°F), which shifts and flattens the peak gain into upstairs rooms on hot afternoons with little effect on annual energy.
4 · Air and the boundary: where the envelope is, and where it leaks
Bottom line. The insulation and the air barrier have to sit on the same continuous surface; where they separate, the insulation is bypassed.
The air barrier is a continuous plane, coincident with the insulation
Fibrous insulation is air-permeable, so it insulates only where a continuous air barrier sits against it. At the ceiling the barrier is the gypsum plane with its penetrations sealed; in walls it is the gypsum and the sheathing with their edges and penetrations sealed; at the garage it is the gypsum fire membrane. An insulation layer with an open air space on its warm side forms a ventilated cavity with little resistance.
Leakage is rated by a blower-door test as ACH₅₀ (air changes per hour at 50 Pa). Houses of this era typically test at 5–8 ACH₅₀. The flow at other pressures follows a power law.
Q airflow, cfm · ΔP pressure difference, Pa · n flow exponent (0.5 for a sharp orifice, 1 for laminar)
leakage grows less than in proportion to the pressure driving it.
At the ceiling, stack-driven leakage rivals conduction
Ceiling and atticExterior wallsGarage boundarySlab
Informs D1
h height above the neutral pressure plane, m · T absolute temperatures, K · P_atm 101,325 Pa
warm air is lighter than outdoor air, so the top of the house is pushed outward harder the colder it is outside.
The neutral plane sits where inflow and outflow balance. With 35% of the leakage in the ceiling plane, typical for the vintage, and the rest spread over the walls, it rises to about 3.8 m in a 5.5 m two-story house, and at 70 °F inside and 35 °F outside the ceiling sees about 1.4 Pa (Figure 7). A 6 ACH₅₀ reference house then pushes about 63 cfm through the ceiling, a UA equivalent of 68 Btu/h·°F against 48 for R-30 conduction and 34 at nominal R-49. Placing the neutral plane at mid-height, a common simplification, gives 87 cfm and is an upper bound.
| House ACH₅₀ | Ceiling leak UA | vs R-30 conduction | vs R-49 conduction |
|---|---|---|---|
| 3 | 34 | 0.7× | 1.0× |
| 4.5 | 51 | 1.1× | 1.5× |
| 6 | 68 | 1.4× | 2.0× |
| 8 | 90 | 1.9× | 2.6× |
| 10 | 113 | 2.4× | 3.3× |
35% of leakage in the ceiling plane, n 0.65, neutral plane by mass balance, no wind. In mild weather the stack term falls with ΔT and the two terms converge; the annual-average whole-house rate in Table 2 is lower than this design-hour flow for that reason.
At the reference leakage the ceiling plane passes 1.4–2.0 times its R-30 conduction and 2.0–2.7 times its R-49 conduction at design conditions, the range spanning the two neutral-plane assumptions (Table 8). Deepening insulation raises the ratio because it lowers only the conduction term. Near 3 ACH₅₀, or with a much smaller ceiling share, conduction at R-49 becomes the larger term; a blower-door test with a zone-pressure diagnostic measures both.
Recessed downlights and partition top plates are usually the two largest categories of ceiling leakage (Figure 8). Fixture type and count are a lighting decision; the partition head under trusses is a joint designed to move (Framing · Truss uplift). Airtightness and stiffness are separate properties, so a flexible continuous seal closes that joint for air and sound at once (Soundproofing · The partition-head gap).
The garage puts two boundary surfaces inside the footprint
Ceiling and atticExterior wallsGarage boundarySlab
Informs D3
The boundary is one closed surface between conditioned and unconditioned volume (Figure 9). Interior partitions and the floor between stories are inside it and carry no thermal requirement. The garage is inside the footprint and outside the boundary, so the walls it shares with the house and the floor of the rooms above it are boundary surfaces, mandated today at R-15 for 2×4 walls and R-19 for floors. A crew that treated the garage ceiling as an interior floor left it empty or part-filled, and nothing visible distinguishes the two.
| Assembly | U | Effective R |
|---|---|---|
| Floor over garage, empty bay | 0.214 | 4.7 |
| R-19 batt, held against the subfloor | 0.047 | 21.3 |
| R-30, bay filled | 0.034 | 29.7 |
| Garage–house wall, empty | 0.268 | 3.7 |
| Garage–house wall, R-15 | 0.081 | 12.3 |
Floor: 9¼ in sawn joists at 16 in, 10% framing, ¾ in subfloor, ⅝ in Type X below. Wall: 2×4, gypsum both sides, 25% framing.
R-19 in a 9¼ in bay leaves about 3¾ in of air above the batt. Held against the subfloor it behaves as calculated; left to sag, the air layer above it connects to the garage through gaps at the rim and the assembly matches neither row of Table 9. The gypsum is also the fire separation (CRC R302.6) and the barrier against garage CO and fuel vapors (R302.5), so every penetration is a contaminant path before it is an energy one.
5 · Moisture: drying direction and vapor control
Bottom line. In IECC zone 3 a stucco wall can dry toward the interior, and a low-perm interior layer removes that path; moisture reaches the attic by air, not by diffusion.
Two climate-zone systems share digits and mean different things
Title 24 energy climate zones (16 zones, by ZIP code in Reference Joint Appendix JA2) set energy values. The IECC/ASHRAE 169 zones set the CRC moisture rules: most of coastal and inland California is 3C (warm-marine) or 3B, with Marine 4 on parts of the north coast. CRC R702.7 requires an interior Class I or II vapor retarder only in Marine 4 and zones 5–8, so a Title 24 "zone 4" house is usually not a "zone 4" house for vapor purposes.
A vapor-open interior lets a stucco wall dry inward
Ceiling and atticExterior wallsGarage boundarySlab
Informs D2
Stucco stores rain and dew, and sun drives that moisture inward in warm weather. A vapor-open interior (unfaced fill, latex-painted gypsum, Class III at about 3–10 perms) lets it leave; a low-perm interior layer stops it at the back of the gypsum (Figure 10). In winter the outdoor side is not cold for long enough to drive significant outward condensation.
Table 10 sets out the vapor rule for each assembly.
| Assembly | Code | What the physics implies | What fails |
|---|---|---|---|
| Exterior wall, cavity fill only | No interior vapor retarder in 3B or 3C | Unfaced fill and latex paint keep inward drying | Kraft facing or polyethylene on the warm side |
| Exterior wall with interior continuous insulation | No retarder required | Mineral wool board keeps inward drying; foam leaves outward only and needs the foam face above dew point | Foam plus polyethylene or kraft: two low-perm layers with a wettable cavity between |
| Vented attic ceiling | Air sealing (CZ 2, 4, 8–16 when §150.2(b)1J applies); ventilation per CRC R806 | Air sealing is the moisture control; ventilation removes what arrives | A vapor barrier at the ceiling with the leaks left open |
| Slab under a moisture-sensitive finish | A vapor retarder under new slabs; product limits for insulation under a heated topping | Slab relative humidity measured by ASTM F2170 shows whether a bonded finish will stay dry | An impermeable finish on an untested slab of unknown vapor retarder |
6 · Ground and radiant: slab edge, heated slabs, emitter backing
Bottom line. An unheated slab loses mostly at its edge and needs little insulation in a mild climate; a heated slab or an emitter panel needs insulation behind it to deliver its heat to the room.
An unheated slab loses heat at its edge
Ceiling and atticExterior wallsGarage boundarySlab
Informs D4
F slab-edge coefficient, Btu/h·ft·°F · P exposed perimeter, ft
slab loss is set by the length of edge exposed to outdoor air, not by the area.
Soil under a slab warms toward the slab temperature, so the field loses little and the edge dominates. F is about 0.73 for an uninsulated unheated slab and about 1.35 for an uninsulated heated one (ASHRAE 90.1 Appendix A, typical). Title 24 Table 150.1-A requires no slab-edge insulation in climate zones 3–4 for an unheated slab, which matches the mechanism. A slab continuous under an attached garage also loses sideways into the garage slab, a path the perimeter coefficient does not include.
A heated slab or panel loses a share of its output through its back
Informs D4
R_back resistance from emitter to the cold side
the share lost behind an emitter is set by the resistance behind it relative to the resistance to the room.
A slab delivering 15 Btu/h·sf to a 70 °F room runs near 80 °F at the tubing. Over ground at about 60 °F the field of an uninsulated slab loses about a quarter of its output, and the perimeter band, which loses toward outdoor air (35 °F at design), about two thirds; a new topping over R-10 board loses under a tenth (Figure 11). A ceiling panel follows the same rule against the attic: insulation in contact keeps the loss to 8% or less, the eave taper raises it to 20%, and an air gap open to the attic to about 63%. Contact is a physical requirement rather than a code number; the inputs are in Table 11.
Inputs and results for the back-loss cases
| Emitter and backing | R_back | q_back, Btu/h·sf | Share lost |
|---|---|---|---|
| Field, uninsulated | 4.0 | 5.0 | 25% |
| Perimeter band, uninsulated | 1.5 | 30.0 | 67% |
| Topping over R-5 | 9.0 | 2.2 | 13% |
| Topping over R-10 | 14.0 | 1.4 | 9% |
| R-49 in contact | 49.0 | 1.1 | 5% |
| R-30 in contact | 30.0 | 1.8 | 8% |
| Eave taper, at the wall line | 10.5 | 5.2 | 20% |
| Air gap open to the attic | 1.5 | 36.7 | 63% |
Slab: 15 Btu/h·sf to the room; field toward 60 °F ground, edge toward 35 °F outdoor air. Ceiling panel: 90 °F surface, 21 Btu/h·sf to the room, attic at 35 °F. Emission coefficients from HVAC · Radiant emission.
Three slab configurations differ in which loss they treat (Figure 12). Vertical perimeter insulation acts on the edge only. A topping over continuous board treats both, separates the emitter from the old slab's mass, which shortens its response, and raises the finished floor about 3½ in, with consequences for doors, stair risers and thresholds, and a gypsum-concrete topping adds about 14 psf of dead load where it sits on framing (Framing · Added floor dead load). Which geometry the code accepts is in Part 8.
7 · Interior cavities: fill for sound and fire
Bottom line. Most new fill in an interior remodel goes into partitions and the floor between stories, where it serves acoustics and fire, not heat.
Cavity fill for acoustic assemblies: airflow resistivity, not density
Fibrous fill damps the cavity resonance of a double-leaf wall and absorbs standing waves (Soundproofing · Lowering f₀). The governing property is airflow resistivity σ: below about 5,000 Pa·s/m² sound passes through, above about 30,000 the surface reflects, and the common products sit inside that band.
Table 12 compares the candidate fills on this property.
| Material | σ, Pa·s/m² | Behavior in a partition |
|---|---|---|
| Fiberglass batt | 8,000–15,000 | In band |
| Mineral wool batt | 20,000–35,000 | Upper band |
| Cellulose, dense-pack | 10,000–25,000 | In band; needs netting in open walls |
| Open-cell spray foam | far above the band | Air-impermeable at common thicknesses; bonds to both leaves |
| Closed-cell spray foam | closed cell | Not an absorber; bonds both leaves rigidly |
Spray foam of either type glues the two leaves together and restores the bridge that decoupling removes (Soundproofing · Coupling). Mineral wool and glass fiber batts meet the acoustic requirement and are accepted as fireblocking in specified applications (CRC R302.11.1), where solid blocking across both leaves of a double-stud wall would bridge it (Soundproofing · What does bind).
| Material | R per in | Vapor | Distinguishing property |
|---|---|---|---|
| Fiberglass batt | 3.7–4.3 | Open | Lowest cost per R; performance limited by fit around wiring and boxes |
| Mineral wool batt | 4.0–4.3 | Open | Holds shape, non-combustible (ASTM E136); 1.5–2× fiberglass cost |
| Blown cellulose | 3.2–3.8 | Open, hygroscopic | High heat capacity; settles 10–20% unless specified by settled depth |
| Loose-fill fiberglass | 2.5–3.5 | Open | Lowest cost for attic depth; little heat capacity |
| Open-cell spray foam | 3.6–3.8 | Semi-open | Air seal and fill in one; bonds to framing; thermal barrier required |
| Closed-cell spray foam | 6.0–7.0 | Class II at 2 in | Highest R per inch; blocks drying; bonds leaves; thermal barrier required |
Table 13 collects the fill materials; rigid boards are in Table 5.
8 · Code, permits and documentation
Bottom line. Title 24 Part 6 binds insulation work, is inspected, and engages component by component as the work touches each one.
Which code, which cycle
The 2025 California Energy Code (Title 24 Part 6) applies to permit applications filed on or after 1 January 2026, with the CRC (Part 2.5) setting ventilation clearance, vapor retarders, fire separations and foam barriers. AB 130 (2025) bars changes to residential building standards until 1 June 2031, so this cycle is likely to govern through most remodels started now. Local reach codes adopted before the freeze may still apply.
Three tiers: mandatory, prescriptive, alteration
Informs D5
Table 14 sets out the three tiers. The mandatory tier always applies; prescriptive or performance compliance sits on top of it.
| Tier | Requirement (as summarized) | Role here |
|---|---|---|
| Mandatory (§150.0, §110.7, §110.8) | Ceiling U-0.043 / R-22; walls U-0.095 / R-15 in 2×4 and U-0.069 / R-21 in 2×6 (2025); raised floors R-19; sealing; certified insulation, facings in contact | Applies to any altered component on any path |
| Prescriptive, new construction (Table 150.1-A) | Wall U-0.048 in CZ 3–4; vented-attic ceiling R-30 in CZ 2–7 (Option C, 2025); slab edge not required in CZ 3–4; QII | A benchmark, and the standard design on the performance path |
| Alteration (§150.2(b)) | Altered 2×4 walls R-15, with an exception for existing R-11; vented attic R-49 or U-0.020 in CZ 1–4, 6 and 8–16, air sealing in CZ 2, 4 and 8–16, downlights covered; no continuous insulation where siding stays | The tier that governs an interior remodel |
The alteration rules accept cavity-only insulation where cladding stays because of the framing cap in Part 2. The performance path (§150.2(b)2) models each altered component against the higher of code or its existing condition and lets surpluses offset deficits; Quality Insulation Installation (Reference Appendix RA3.5) then becomes a modeled credit verified by an ECC rater (the 2025 title for the former HERS rater).
Each provision engages only when the work touches its component
Figure 13 draws the triggers.
The ceiling provision is the one most open to reading. §150.2(b)1J applies to altered vented-attic ceilings, and the HVAC alteration rules cross-reference it when a new or complete replacement duct system is placed in the attic; a hydronic system with no attic ducts may leave it unengaged, while radiant panels fixed to the ceiling may count as altering it. The reading belongs to the building department, and it decides whether R-49 and ceiling air sealing are required or voluntary.
The heated-slab rule assumes a slab being poured
Ceiling and atticExterior wallsGarage boundarySlab
Informs D4
§110.8(g) makes heated slab floors subject to Table 110.8-A on every compliance path, with R-5 in climate zones 1–15. The listed geometries are vertical insulation at the slab edge to 16 in or the frost line, or vertical plus 4 ft horizontal between slab and foundation; both presuppose excavation or a new pour. Insulation in contact with the ground must also limit water absorption (0.3%, ASTM C272, tested without facings) and vapor permeance (2.0 perm/in), which XPS and some high-density products meet and ordinary EPS does not; board laid over an existing slab under a topping is not in ground contact.
A topping over continuous board is thermally stronger than either listed geometry but is not one of them, so its acceptance is an equivalence question for the building department, settled at plan check rather than at inspection.
Table 110.8-A values, geometries and the ground-contact limits are from the 2022 text; the §150.2(b)1J trigger, zones and exceptions and the mandatory ceiling value are from 2025 secondary sources, which do not fully agree. They are confirmed against the adopted 2025 text and the building department's reading before they decide a scope.
CRC provisions that limit what may be installed
| Section | Requirement | Why |
|---|---|---|
| R806.2, R806.3 | Attic vent area 1/150 (1/300 with balanced upper vents); 1 in clear at eave vents; baffles | Creates the eave taper; vent paths are the attic's moisture control |
| R806.5 | Unvented attics: air-impermeable insulation at the deck to a minimum R; no interior Class I retarder | The deck must stay above dew point because it cannot dry to outdoors |
| R702.7 | Interior Class I or II retarders only in Marine 4 and zones 5–8 | Keeps inward drying in zone 3 |
| R302.6, R302.5 | Garage separation gypsum (⅝ in Type X under habitable rooms); limits on openings and ducts | Fire and CO; insulation fills the rated assembly, not the reverse |
| R302.11 | Fireblocking at floors, ceilings and 10 ft; mineral wool or glass fiber accepted in specified uses | Stops concealed spaces acting as chimneys |
| R316 | Foam plastic separated from the interior by a thermal barrier, ½ in gypsum or equivalent | Foam ignites readily and smokes heavily |
Table 15 lists the CRC constraints. The energy compliance documents are the CF1R (design, at plan check), CF2R (installation, signed by the installer) and CF3R (field verification by the ECC rater where a measure requires it, such as QII); the inspector checks the CF2R against the work before drywall.
Where it goes wrong
- Insulating over an unsealed ceiling. Loose fill does not stop air; it buries the leaks and makes the attic surfaces above them colder, where exfiltrating air leaves its moisture (Part 4).
- Sealing the partition head rigidly, or not at all. Hard caulk cracks with the first winter's truss movement; an open joint is a leak and a sound path (Part 4).
- Blocking eave vents with new depth. Without baffles the fill closes the soffit vents and violates the 1 in clearance (Part 3).
- Reading nominal R as assembly performance. R-15 batts make an R-12 wall; R-49 at a standard heel is about R-40 (Part 2, Part 3).
- Batts compressed or gapped. A ¼ in gap at a stud or a batt split behind a box sets up convection; field studies place poor installations 20–30% below nominal, which is what QII inspects.
- A vapor retarder because of "zone 4". The Title 24 zone is not the IECC zone; kraft or polyethylene on the warm side of a zone 3 stucco wall removes its drying path (Part 5).
- Missing the garage boundary. Two surfaces inside the footprint carry about a quarter of the reference UA and are a CO path (Part 4).
- A gap behind a radiant panel. Insulation present but not in contact costs over half the output and passes inspection (Part 6).
- Spray foam in a decoupled partition. It bonds the leaves and gives back the decoupling (Part 7).
- Ordinary EPS as perimeter insulation in ground contact. It fails the §110.8(g) absorption limit (Part 8).
- Exposed kraft facings in an attic or garage fail the §110.8(c) flame-spread limits unless in contact with a finish; inspectors check this at the insulation inspection.
- Closing the ceiling before the fixture plan is final. Every later downlight is a new hole in a buried plane (Part 4).
Reference
Glossary
- ACH₅₀
- Air changes per hour at a 50 Pa blower-door pressure.
- Air barrier
- The continuous plane that stops bulk air movement through an assembly.
- ECC rater
- Energy Code Compliance rater; the 2025 Title 24 name for the third-party verifier formerly called a HERS rater.
- F-factor
- Slab-edge heat loss per foot of exposed perimeter per °F.
- Framing fraction
- Share of an assembly's area occupied by framing.
- Heel height
- Vertical space between the wall top plate and the roof sheathing where a truss bears.
- Neutral pressure plane
- Height at which indoor and outdoor pressure are equal under stack effect.
- Parasitic fraction
- Share of an emitter's output lost through its back.
- Perm
- Unit of water-vapor permeance; Class I ≤ 0.1, Class II 0.1–1, Class III 1–10.
- QII
- Quality Insulation Installation, Reference Appendix RA3.5.
- Settled depth
- Depth of blown fill after settling; the specification for cellulose.
- UA
- Area times U-factor; heat flow per °F of temperature difference.
Formula sheet
Figure color legend
Red: deficient, or fails the stated criterionAmber: marginal or conditionalGreen: meets the criterionGray: existing or baselineTeal: neutral quantity, reference line or annotation; never a grade
Insulation is drawn in tan, rigid foam in blue-gray, wood, concrete and soil in their material colors; these are materials, not grades.
Code points to confirm
- §150.0(a) mandatory ceiling value in the 2025 text
- §150.2(b)1J trigger, climate zones, air-sealing zones and exceptions (existing R-38; limited space); the building department's reading for a project with no attic ducts
- Altered-wall requirement and the existing-R-11 exception in §150.2(b)1
- Table 110.8-A values, geometries and material limits; whether a topping over continuous insulation is accepted as equivalent
- Table 150.1-A ceiling Option C and radiant-barrier requirement by zone
- Climate zone of the parcel in Reference Joint Appendix JA2
Sources
- California Energy Commission, What's New for 2025: Single-Family (2025) — §150.0(c) 2×4 U-0.095 / R-15, 2×6 U-0.069 / R-21; Option C ceiling R-30 in CZ 2–7.
- 3C-REN, 2025 Energy Code in Practice: Single Family Additions and Alterations (March 2026) — altered walls, §150.2(b)1J R-49 or U-0.020, air sealing and downlight rules.
- California Energy Commission, Residential Compliance Manual, Chapter 3 (building envelope) and Reference Appendices JA2, JA4, RA3.5.
- 2025 California Residential Code, R302.5, R302.6, R302.11, R316, R702.7, R806.
- ASHRAE 90.1 Appendix A (slab F-factors, framing fractions); ASHRAE Handbook — Fundamentals (stack effect, film coefficients); ISO 11855 (radiant surface coefficients).
- California Building Standards Commission, Information Bulletin 25-03 (AB 130).
- Companion guides: Framing, Soundproofing, Windows & Exterior Doors, HVAC, DHW & Ventilation (set v2).
Set v2 draft 1, 2026-10-23: rewritten as a generic theory guide to spec set v2 from the v1 guide (archived). Updated to the 2025 wall values; leakage now uses n 0.65, a mass-balance neutral plane and a 35 °F winter design, which lowers the ceiling leakage ratio from v1's 2.9× to 1.4–2.0×; continuous insulation recomputed by parallel paths (R-7.6, not R-8.7); hip and gable taper separated; heated-slab material limits limited to ground contact after review. Values from one script.